Fluke 369 True-rms Leakage Current Clamp Meter

60,427.36

(12% VAT Included)

DELIVERY:

EX-STOCK: within 7-10 days

INDENT ORDERS: 4-8 weeks

CONTACT US NOW FOR SPECIAL DISCOUNT! 

+632 82515156 / +632 82570795

Fluke 369 True-rms Leakage Current Clamp Meter

Reduce downtime – Find leakage currents without taking equipment offline

The Fluke 369 FC true-rms leakage current clamp meter helps users detect, document, record and compare leakage current readings over time as a means of preventing unplanned downtime, and identifying intermittent GFCI and RCD trips, all without taking equipment off line.

Electrical Specifications
Measurement function Alternating current
AC ampere range 3 mA, 30 mA, 300 mA, 3 A, 30 A, 60 A
Range selection mA / A: manual selection
3 mA / 30 mA / 300 mA: automatic selection
3 A / 30 A / 60 A: automatic selection
Range / Resolution 3 mA¹ / 0.001 mA
30 mA / 0.01 mA
300 mA / 0.1 mA
3 A / 0.001 A
30 A / 0.01 A
60 A / 0.1 A
Accuracy – filter activated (40 to 70 Hz), filter off (40 to 1 kHz)² 3 mA – 30 A
60 A
1% + 5 digits
2% + 5 digits
Frequency 40 Hz to 1 kHz
Crest Factor 3
After calibration accuracy is valid for one year. Accuracy is expressed as ± (% of reading + digits). Reference conditions 23 ±5 °C and a maximum relative humidity of 80%.
¹The minimum value is 10 μA rms.
²Outside of the TC / °C 18 °C to 28 °C, 0.02 + 1
Physical
Display (LCD) Digital readout: 3300 count
Display refresh rate 4 times / sec
Maximum conductor diameter 61 mm
Dimensions 257 x 116 x 46 mm
Weight 600 g
Battery 2 AA, IEC LR6, NEDA 15A, alkaline
Battery life Expected battery life, without using backlight and spotlight, is more than 150 hours
Automatic shut-down Meter automatically shuts down after 15 minutes of inactivity
Safety and Environmental Specifications
General safety IEC 61010-1: Pollution Degree 2
Measurement safety IEC 61010-2-032: CAT III 600 V / CAT IV 300 V
Operating temperature -10 °C to +50 °C
Storage temperature -40 °C to +60 °C
Operating humidity Non-condensing (<10 °C)
90% relative humidity (10 °C to 30 °C)
75% relative humidity (30 °C to 40 °C)
45% relative humidity (40 °C to 50 °C)
Protection class IEC 60529: IP30 (jaw closed)
Operating altitude 2000 m
Storage altitude 12000 m
Current sensor action category IEC 61557-13: Class 2, ≤30 A / m

Key features

  • True-rms measurements for accuracy when measuring complex, non-sinusoidal waveforms
  • 61 mm jaw opening
  • Highest resolution of 1 μA, measure up to 60 A
  • Selectable filter function removes unwanted noise
  • Max/Min/Average readings and hold function
  • Forward-facing LED worklight for use in dark wiring cabinets
  • Backlit display; auto backlight off and auto power off for extended battery life
  • CAT III 600V safety rating

For more details about this product, download Fluke 369 Data sheet.