What Is A Clamp Meter?

General Definition…

A clamp meter is an electrical test tool that integrates a basic digital multimeter with a current sensor.

Basically, clamps measure current. Meanwhile, probes measure voltage. Having a hinged jaw joined into an electrical meter allows technicians to clamp the jaws around a wire, cable, or other conductors at any point in an electrical system, then measure current in that circuit without disconnecting/de-energizing it.

Ultimately, underneath their plastic moldings, hard jaws consist of ferrite iron and are engineered to detect, deliberate, and measure the magnetic field being produced by current as it flows through a conductor.

  1. Current-sensing jaw.
  2. Tactile barrier (to protect fingers from shocks).
  3. Hold button: Freezes the display reading.
  4. Dial (aka rotary switch).
  5. Display.
  6. Backlight button.
  7. Min Max button – Can be triggered depending on the amount of pushes.
  8. Inrush current button.
  9. Zero buttons (yellow): Removes dc offset from dc current measurements. Also serves as the dial’s shift button to select yellow functions scattered around the dial.
  10. Jaw release lever.
  11. Alignment marks – To meet accuracy specifications.
  12. Common input jack.
  13. Volts/ohm input jack.
  14. Input for the flexible current probe.

Formerly created as a single-purpose test tool, recent clamp meters provide more measurement functions, greater accuracy, and in some cases specialized measurement features. In line with this, today’s clamp meters include most of the straightforward functions of a digital multimeter (DMM), such as the capability to measure voltage, continuity, and resistance.

Clamp meters have developed popular tools primarily for two reasons:

  • Safety. Clamp meters allow electricians to avoid the old-school process of cutting into a wire and inserting a meter’s test leads into the circuit to take an in-line current measurement. As a result, the jaws of a clamp meter do not need to touch a conductor throughout a measurement.
  • Convenience. During a measurement, it is not compulsory to shut off the circuit carrying current—a big boost in efficiency.

When measuring high levels of current, an ideal tool is a Clamp Meter. Meanwhile, DMMs cannot measure 10 A of current for more than 30 seconds without risking damage to the meter.

Also, clamp meters propose a minimum current range of 0 A to 100 A. Many models have an array of up to 600 A. Others go up to 999 A or 1400 A, and some plug-in clamp accessories such as the iFlex® can measure as high as 2500 A.

However, industrial equipment, industrial controls, residential/commercial/industrial electrical systems, and commercial/industrial HVAC, are used under Clamp meters.

  • Service: To repair existing systems on an as-needed basis.
  • Installation: To troubleshoot installation problems, perform final circuit tests, and supervise apprentice electricians while installing electrical equipment.
  • Maintenance: To perform scheduled and preventative maintenance as well as system troubleshooting.

Three types of clamp meters exist:

  • Current transformer clamp meters: measure only alternating current (ac).
  • Hall Effect clamp meters: measure both alternating current and direct current (ac and dc).
  • Flexible clamp meters: employ a Rogowski coil; measure ac only; good for measuring in tight spaces.

VISIT OUR WEBSITE AND SHOP NOW: Clamp Meters Archives – Presidium PH

Read more

Diagnosing Power Problems At The Receptacle

By determining hot-neutral voltage, neutral-ground voltage, and hot-ground voltage you are well on your way to answering these receptacle fault questions:

  • Is the outlet wired incorrectly?
  • Is the branch circuit too heavily loaded?
  • Do sensitive electronic loads have the voltage they need?

Basically, these three measurements, all occupied speedily at one outlet, deliver you with a solid acceptance of the building’s electrical supply.

Testing a three-slot receptacle for grounding polarity

Basically, inaccurately wired receptacles are not unusual. A three-slot receptacle has a hot slot (short), a neutral slot (long), and a grounding slot (U-shaped). Are the hot (black) and neutral (white) wires reversed? Are the neutral and ground (green) wires reversed or shorted?

Ultimately, these conditions can go unnoticed for a long time. Many loads aren’t delicate to polarity—they don’t care if hot and neutral are reversed. In contrast, sensitive electronic loads such as computer equipment and instrumentation do care about clean ground – a ground with no voltage and no-load currents on it. A single reversed neutral and ground can cooperate with the entire ground system.

Here’s what you can find.

Hot-neutral is the load voltage. Voltage should read about 120 V (typically 115 V to 125 V). You measure exactly 118.5 V.

  • Neutral ground is a voltage drop (also called IR drop) caused by load current flowing through the impedance of the white wire. Let’s say you measure 1.5 V.
  • The hot ground can be thought of as the source of voltage available at the receptacle. You read 120.0 V. Therefore, you note that hot-ground is higher than hot-neutral. In fact, the hot-ground is equal to the sum of the hot-neutral and neutral-ground voltages.

Are these readings normal? Is the outlet wired correctly?

How to detect mis-wired receptacles

The most common mis-wiring occurs if hot and neutral are switched, or if neutral and ground are either switched or shorted. How do you spot these conditions?

  1. Measuring hot-neutral by itself does not tell you if they’ve been switched. You need to measure neutral-ground or hot-ground. If neutral-ground voltage is about 120 V and hot-ground is a few volts or less, then hot and neutral have been reversed.
  2. Below load conditions, there should be some neutral-ground voltage – 2 V or a little bit less is pretty typical. If neutral-ground voltage is 0 V – again assuming that there is a load on the circuit – then check for a neutral-ground connection in the receptacle, whether accidental or intentional.
  3. In checking if neutral and ground are switched, measure hot-neutral and hot-ground under load. In line with this, Hot-ground should be greater than hot-neutral. The greater the load, the more the difference. If hot-neutral voltage, measured with the load on the circuit, is greater than hot-ground, then the neutral and ground are switched. This is a probable safety hazard and the condition should be modified immediately.

Remember…

Hot-ground reading should be the highest of the three readings. Therefore, the ground circuit, under normal, non-fault conditions, should have no current and therefore no IR drop on it. You can think of the ground connection as a wire running back to the source (the main panel or the transformer), where it’s connected to the neutral. On the receptacle end of the ground path, where the measurement is being made, the ground is not connected to any voltage source (again, assuming there is not a fault). So the ground wire is like a long test lead back to the source voltage.

When there is a load connected, the hot-ground receptacle source voltage should be the sum of the hot-neutral voltage (the voltage across the load) and the neutral-ground voltage (the voltage drop on the neutral all the way back to its connection to the ground circuit).

Finally, if you want to know more about Fluke tools, don’t hesitate to browse in one of Philippines’ authorized distributors, Presidium.PH!

Read more

What Is Resistance?

A General Description…

“Ohms” is another way to call this element. Initially, it is a hindrance to the movement of electrons in the material. While a potential difference across the conductor encourages the flow of electrons, resistance discourages it. The rate at which charge flows between two terminals is a combination of these two factors.

All materials resist current flow to some degree. They fall into one of two broad categories:

Conductors: Materials that offer very little resistance where electrons can move easily. Examples: silver, copper, gold, and aluminum.

Insulators: Materials that present high resistance and restrict the flow of electrons. Examples: Rubber, paper, glass, wood, and plastic.

Initially, these measures are taken to specify a component or a circuit. The elevated the ohms are, the lower the current flow. If it is too high, a possible cause can be damaged conductors because of burning or corrosion. Overheating is a definite issue of resistance. This is because all conductors give off some degree of heat. They reduce impedance, the greater the current flow. Possible causes: insulators damaged by moisture or overheating.

Keep in mind…

Many components, such as heating elements and resistors, have a fixed-resistance value. These values are often printed on the components’ nameplates or in manuals for reference. The measured value should be within the specified resistance range. Any significant change in the said component value usually indicates a problem. This element may sound negative, but electricity can provide advantages.

The ohms of a conductor, or circuit element, generally increase with increasing temperature. When cooled to extremely low temperatures, some conductors have zero resistance. Currents continue to flow in these substances, called superconductors, after the removal of the applied electromotive force.

Meanwhile, this can have good and bad effects. If we are trying to transmit electricity from one place to another through a conductor, resistance is undesirable. Why? This is because electrical energy can turn into heat.

Using Ohm’s Law

Accordingly, troubleshooting technicians often determine resistance by taking voltage and current measurements and applying Ohm’s Law:

E = I x R

That is volts = amps x ohms. R stands for resistance in this formula. On the other hand, you can also convert the formula to R = E/I (ohms = volts divided by amps). However, this works only when the resistance is unknown.

Finally, if you wish to know more about the best-performing Fluke tools in the market, don’t hesitate to visit our feed

Read more

Peak Efficiency Cogeneration

Cogeneration captures heat from energy-intensive industrial methods and puts it back to work. Basically, steam is the outcome of this process. And that steam can lead to a turbine generator or warm other components of the facility. For instance, heat recovery can increase energy efficiency by 30 percent or more. Cogeneration has accumulated a lot of attention. As a result, sophisticated and almost turnkey cogeneration solutions are now available in a variety of sizes.

Here are the three key areas of the cogeneration process to help your plant maximize productivity.

Enhancing heat recovery

Everything that permits heat to escape from a heat recovery system decreases efficiency. Insufficient or damaged insulation and failed steam traps are two areas that merit close attention. To find failed insulation, begin with a careful visual inspection. A thermal imaging tool is a big help here. Initially, what may look good to the naked eye may look completely different when viewed with a thermal imager. Inspection of all insulated piping and equipment with a thermal imager should be performed annually and after any maintenance that requires the removal of insulation.

Optimizing mechanical systems and equipment

Thermal imaging can also guide with repairing mechanical problems that can diminish the efficiency and reliability of a cogeneration operation. A vibration tester can then track the cause of overheated mechanical parts that have been detected with a thermal imager.

Peak Efficiency Cogeneration: Improving electrical systems

Electrical inefficiencies in cogeneration systems can be in both the electrical generation and distribution system and in electrical equipment that operates as part of the cogeneration system. If the generator of the cogeneration facility is providing a huge number of inductive loads, for instance, motors and transformers, it may be running at a poor power factor. Increasing power factor correction capacitors in the electrical distribution system will innovate the power factor, and more power from the generator will be available to do useful work in the distribution system.

Peak efficiency cogeneration maximizes the power of combined heat and proper with proper measurement and maintenance in three aspects in order to help your plant maximize reliability. Visit https://presidium.ph/ for more information.

Read more